MCB TECHNICAL DATA

Download Catalogue pages, return to Home page or Contact us now.

'B', 'C' & 'D' - CURVE
                   Dimensions                        Characteristics
DLS 6 range - rated up to 63 A

Specifications
Rated breaking capacity

	                    
	                   
Max. operating voltage
Min. operating voltage

Back-up protection(maximum)  

Protection (EN60529)
Positioning
Mounting
Mech. service life

Ambient temperature

Terminal Screws
EN 60898-1
Characteristic B     HB    6 kA
Characteristic B      IB   10 kA
Characteristic C      IC   10 kA
Characteristic D      ID   10 kA
Uemax = 400 V AC,  60 V DC
Uemin =   12 V AC/DC

125 A gL/gG 

IP 20
Optional
on 35mm rail conforming to EN 60715
min. 20.000 switching cycles

-25°C to +55°C

Max. torque 2.5 Nm

Click for large image

HIGH RATING 'C' - CURVE
               Dimensions                      see above for Characteristics
DMCB 2 range - rated 80 A to 125 A
	
Specifications 
Tripping Characteristic          
Max. operating voltage
Min. operating voltage
Breaking capacity 
Ambient temperature
Connection
Terminal Screws
EN 60947-2 
"C" 
Uemax = 400 V, 40/60 Hz, 60 V DC
Uemin =   12 V AC/DC
see table below 
-30oC to +50oC
2.5 - 50 mm²
Max. torque 3.0 Nm
Click for large image

Return to Product Overview or see the range of Wiring Accessories